Show Mobile Navigation

Interesting Articles

,

Residual Current Circuit Breakers (ELCB, RCCB, RCBO)

ELCB is short form of Earth Leakage Circuit Breaker which is a Residual Current device (RCD). RCCB  is also another synonym for ELCB definition of which is Residual Current Operating Circuit Breaker. 

A Residual Current Device (RCCB, ELCB, RCBO etc.) is a device that is designed to provide protection against electrocution or electrical fires by cutting off the flow of electric automatically when it senses a 'leakage' of electric current from a circuit. 

Residual Current Devices have the following Specifications 
  • Sensitivity - milli Amperes (mA) 
  • Current Rating - Amperes (A)
  • Short Circuit Rating - Kilo Amperes (kA)
  • Poles - 2 Pole or 4 Pole

Operating Principle of a Residual Current Device

The basic operating principle of a residual current device is given in the figure below.
Operating principle of Residual Current Circuit Breaker

When the load is connected to the supply through the  Residual Current Device (RCD), the line and neutral conductors are connected through primary windings on a toroidal transformer. In this arrangement the secondary winding is used as a sensing coil and is electrically connected to a sensitive relay or solid state switching device, the operation of which triggers the tripping mechanism. 

When the line and neutral currents are balanced, as in a healthy circuit, they produce equal and opposite magnetic fluxes in the transformer core with the result that there is no current generated in the sensing coil. (For this reason the transformer is also known as a 'core balance transformer'). 

When the line and neutral currents are not balanced they create an out-of-balance flux. This will induce a current in the secondary winding which is used to operate the tripping mechanism. It is important to note that both the line and neutral conductors pass through the toroid. 

A common cause of unwanted tripping is failure to connect the neutral through the RCD, RCDs work equally well on single phase, three phase or three phase and neutral circuits, but when the neutral is distributed it is essential that it passes through the toroid. 

Test Circuit 
A test circuit is always incorporated in the RCD. Typically the operation of the test button connects a resistive load between the line conductor on the load-side of the RCD and the supply neutral. 

Working of a Residual Current Device 

In an RCD, the line and neutral conductors of a circuit pass through a sensitive current transformer. If the line and neutral currents are equal and opposite, the core remain balanced (Figure A). 

If there is an earth fault the neutral current will be lower than the line current. This imbalance produces an output from the current transformer which is used to trip the RCD and so break the circuit (Figure B).
Working of  Residual Current Device
RCDs normally don't offer protection against current overloads: RCDs detect an imbalance between the live and neutral currents. A current overload, however large, cannot be detected. If a line neutral fault occurs (a short circuit, or an overload), the RCD won't trip, and may get damaged. 

In practice, the main Miniature Circuit Breaker (MCB) for the premises will probably trip, or the service fuse so the situation is unlikely to lead to catastrophe, but it may be inconvenient. 

It is now possible to get an MCB and RCD in a single unit, called an RCBO. Replacing an MCB with an RCBO of the same rating is generally safe. RCBO is Residual Current Circuit Breaker with Overcurrent Protection.

Standard ratings available are 25A, 40A, 63A and 100A 

Standard Sensitivities available are 30mA. 100mA, 300mA and optionally 10mA is also available. Electromechanical RCCBs are designed to operate on normal supply waveforms and cannot be guaranteed to operate where none standard waveforms are generated by loads. The most common is the half wave rectified waveform sometimes called pulsating dc generated by Computers, Speed control devices (VFD) and even dimmers.